Factory programming will load all standard features and customer-specified options per the default settings.
In-phase monitor is a feature that will allow a transfer between two sources only when the phase difference between the two sources is near zero. This is an open transition transfer that prevents in-rush currents from exceeding normal starting currents in the case where motor loads are being transferred.
Load voltage decay transfer is a feature that, after opening the switch for the original source, holds in the neutral position until the voltage on the load is less than 30% of rated voltage. This operation is an open transition that prevents in-rush currents from exceeding normal starting currents in the case where motor loads are being transferred.
Rating Range | 120 to 600V, single phase and three phase @ 50/60 Hz |
Transfer Type | Switch application dependent |
Switch Type | Switch application dependent |
Input Control Voltage | 120Vac (50/60 Hz) (operating range 65 to 160 Vac) |
Voltage Measurements of Utility | Source 1, Source 2 and Load<br>(VAB, VBC, VCA for Three Phase System) |
Voltage Measurement Range | 0 to 700 Vac |
Voltage Measurement Accuracy | +/-1% of full scale |
Frequency Measurements Of | Source 1 and Source 2 |
Frequency Measurement Range | 40 Hz to 80 Hz |
Frequency Measurement Accuracy | +/- 0.1 Hz |
Undervoltage Dropout | Breaker Style 50 to 97% of Nominal System Voltage<br>Contactor Style - 78 to 97% |
Undervoltage Pickup | (Dropout +2%) to 99% of Nominal System Voltage |
Underfrequency Dropout Range | 90 to 97% of Nominal System Frequency |
Underfrequency Pickup Range | (Dropout +1 Hz) to 99% of Nominal System Frequency |
Overfrequency Dropout Range | 103 to 110% of Nominal System Frequency |
Overfrequency Pickup Range | 101% to (Dropout +1 Hz) of nominal system frequency |
Operating Temperature Range | -20 to 70 degree C (-4 to +158 degree F) |
Operating Humidity | Up to 90% Relative Humidity (non-condensing) |
Enclosure Compatibility | <li>NEMA 12 (std mounting)</li><lNEMA 4/4X</li><li>NEMA 3R</li><li>UV Resistant Faceplate</li> |
System Voltage Application | 120 to 600 Vac (50/60 Hz) (single or three phase) |
Product specifications, standard and optional equipment may vary depending on stock availability. For more information or to verify specific product details, please get in touch with one of our sales representatives.