MX350 Controller

Overview

The MX350 controller is specifically designed for low voltage Automatic Transfer Switch (ATS) applications. The flexible control and communications options are ideal for any application. Integrated push buttons, graphical controls and LED indicators reduce external components and wiring in addition to providing local control and access to system information. Multiple communication protocols allow simple integration into monitoring and control systems.

Image shown may not reflect actual package.

 

Enquire
Controller Specifications
Voltage Unbalance on Dropout for Source 1 and Source 25 to 20% of nominal
Delay NeutralTransition Time Delays (DT,DW)0-10 minutes
Control Power120 VAC
Undervoltage Dropout for Source 1 and Source 275-99% of nominal
Undervoltage Restore for Source 1 and Source 285-100% of nominal
Overfrequency Dropout for Source 1 and Source 250.1 - 63 Hz
Source Sensing120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A)
Delay for Engine Cool Down (U)0-60 minutes
Underfrequency Restore for Source 1 and Source 245 - 59.5 Hz
Load Control Relay Contacts (2)0-259 minutes
Overvoltage Dropout for Source 1 and Source 2105 - 110% of nominal
Voltage Unbalance for Restore for Source 1 and Source 24 to 19% of nominal
Storage Temperature(-40˚C - 90˚C )
Underfrequency Dropout for Source 1 and Source 245 - 59.9 Hz
Overfrequency Restore for Source 1 and Source 250 - 62.9 Hz
Delay Transfer to Nonpreferred Source (W)0-5 minutes
Operating Temperature Ambient(-20˚C to 50˚C)
Communications Interface - OptionalSerial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T)
Overvoltage Restore for Source 1 and Source 2103 - 108% of nominal
Load Control Relay Contacts (1)rated for 10A @ 24VDC or 120VAC
Technical Summary
Rating RangeSwitch Dependent
Transfer TypeApplication Dependent
Switch TypeApplication Dependent
Status LEDS for:
Transfer Inhibit
Active Alarms
Source 1 and 2 Availablity
Source 1 and 2 Connected
Time Delay Active
Graphical Display:
Color graphical display with USB Calibration/programming port and Embedded Help
Displays 256 time-tagged events with 1 ms resolution
Monitors over/under frequency, voltage conditions, frequency imbalance, and phase rotation
Provided detailed outage,test,and diagnostic reports
Ranges of Controls / Metering:
Programmable generator exerciser
Synchroscope
Contacts for Source 1 and Source 2 position indication as well as remote load test signals, and engine start delay
Source 1 and Source 2 In-phase monitor
Neutral, Engine Start, and Engine stop time delay timers
Testing and Certification
Conforms to EN 60947-1, EN 60947-6-1, EN 60255-26 (EN 50263), EN 5502 / CISPR22 / EN 61000-6-2 / EN 61000-6-4
Tested in accordance with:
IEC 60068-2-30
IEC 60068-2-1
IEC 60068-2-2
IEC 60255-22-1
IEC 60255-22-2
IEC 60255-22-3
IEC 60255-22-4
IEC 60255-22-5
IEC 60255-22-6
IEC 60255-25
IEC 60529; IP54 (front),IP20(back)
IEC 61000-4-11
Quality System:
Manufactured under an ISO 9001 Registered Program
Features and Benefits
  • Dual Communications
    Built-in RS-485 serial and 10/100 base-T Ethernet
    Open protocols - Modbus RTU and Modbus TCP
  • Available to support Open, Closed and Delayed Transition
  • Small footprint
  • Graphical control panel
  • Multiple communication protocols
  • ¼ inch VGA color graphical display with embedded HELP menus
  • Status LED's indicating:
    ALARM - indicating a problem with the ATS or a user configured alarm condition is active
    TD DELAY - indicating the controller is timing before taking the next control action
    XFER INHIBIT - indicating the controller will not transfer to the other source without operator intervention
    SOURCE 1(S1) AVAILABLE LED - indicating power is present per user setpoints
    SOURCE 2 (S2) AVAILABLE LED - indicating power is present per user setpoints
    SOURCE 1 (S1) STATUS LED - indicating load is connected to S1 power
    SOURCE 2 (S2) STATUS LED - indicating load is connected to S2 power
  • User-Configurable setpoints for inputs and Outputs
  • Field modification of control features
  • Plant exerciser clock for 1 day, 1 week, 14 days, 28 days or 365 days. The time base of 365 days permits up to 24 events to be scheduled and the other time bases permit up to 24 events.
  • SYSTEM TESTS
    Fast Test - test with load, no time delays
    Transfer Load - test with load with time delays
    No Transfer - test without load, generator start only
  • Controller Power Supply utilizing the Universal Transformer Assembly (UTA) - provides 170Vdc to the controller and 24Vdc ungrounded to the power relays. The UTA also provides line voltages from 120Vac to 600Vac via an internal six position jumper array, 120Vac UPS input and 24Vdc input battery options.
  • Dual processor based with dedicated processor for high speed Serial or Ethernet connections
  • All signal in / out relays are isolated via DIN Mounted relay / terminal blocks
  • Elevator pre-signal contacts
  • Power quality metering
  • Elevator pre-signal
Specifications
Controller Specifications
Voltage Unbalance on Dropout for Source 1 and Source 25 to 20% of nominal
Delay NeutralTransition Time Delays (DT,DW)0-10 minutes
Control Power120 VAC
Undervoltage Dropout for Source 1 and Source 275-99% of nominal
Undervoltage Restore for Source 1 and Source 285-100% of nominal
Overfrequency Dropout for Source 1 and Source 250.1 - 63 Hz
Source Sensing120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A)
Delay for Engine Cool Down (U)0-60 minutes
Underfrequency Restore for Source 1 and Source 245 - 59.5 Hz
Load Control Relay Contacts (2)0-259 minutes
Overvoltage Dropout for Source 1 and Source 2105 - 110% of nominal
Voltage Unbalance for Restore for Source 1 and Source 24 to 19% of nominal
Storage Temperature(-40˚C - 90˚C )
Underfrequency Dropout for Source 1 and Source 245 - 59.9 Hz
Overfrequency Restore for Source 1 and Source 250 - 62.9 Hz
Delay Transfer to Nonpreferred Source (W)0-5 minutes
Operating Temperature Ambient(-20˚C to 50˚C)
Communications Interface - OptionalSerial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T)
Overvoltage Restore for Source 1 and Source 2103 - 108% of nominal
Load Control Relay Contacts (1)rated for 10A @ 24VDC or 120VAC
Technical Summary
Rating RangeSwitch Dependent
Transfer TypeApplication Dependent
Switch TypeApplication Dependent
Equipment
Status LEDS for:
Transfer Inhibit
Active Alarms
Source 1 and 2 Availablity
Source 1 and 2 Connected
Time Delay Active
Graphical Display:
Color graphical display with USB Calibration/programming port and Embedded Help
Displays 256 time-tagged events with 1 ms resolution
Monitors over/under frequency, voltage conditions, frequency imbalance, and phase rotation
Provided detailed outage,test,and diagnostic reports
Ranges of Controls / Metering:
Programmable generator exerciser
Synchroscope
Contacts for Source 1 and Source 2 position indication as well as remote load test signals, and engine start delay
Source 1 and Source 2 In-phase monitor
Neutral, Engine Start, and Engine stop time delay timers
Testing and Certification
Conforms to EN 60947-1, EN 60947-6-1, EN 60255-26 (EN 50263), EN 5502 / CISPR22 / EN 61000-6-2 / EN 61000-6-4
Tested in accordance with:
IEC 60068-2-30
IEC 60068-2-1
IEC 60068-2-2
IEC 60255-22-1
IEC 60255-22-2
IEC 60255-22-3
IEC 60255-22-4
IEC 60255-22-5
IEC 60255-22-6
IEC 60255-25
IEC 60529; IP54 (front),IP20(back)
IEC 61000-4-11
Quality System:
Manufactured under an ISO 9001 Registered Program
Benefits & Features