Remote Fuel System 4

  • Remote Fuel System 4

    Remote Fuel System 4 Remote Fuel System 4

    International Enquiries Contact Us

    Within Australia Contact Us

    When set to automatic, low fuel level in the basetank is sensed by the fuel level sensor. The DC motorised valve is opened and the pump
    begins to pump fuel from the bulk tank to the basetank through the supply line. To help ensure that clean fuel reaches the engine, fuel from the
    bulk tank is strained just prior to the motorised valve.

    When the basetank is full, as sensed by the fuel level sensor, the pump stops and the motorised valve is closed. Any overflow into
    the basetank or overpressure in the basetank will flow back to the bulk tank via the extended vent.

    SYSTEM REQUIREMENTS

    • Bulk fuel tank (item 1) above ground*
    • Control panel (item 2)
    • DC motorised fuel valve (item 3)
    • AC fuel pump (item 4)
    • Fuel level switches in the basetank (item 5)
    • Fuel supply line (item 6)*
    • Extended vent/return line (continuous rise) on the basetank (item 7)*
    • Fuel strainer (item 8)
    • Isolating valve at the bulk tank (item 9)*
    • Level gauge (item 10)

    *No included